Lista błędów

Kod błędu Nazwa
00 Not an error
01 15 V disturbed or missing
02 Counterclockwise rotating field on power stage connection or power stage not connected (see also P007)
03 Synchronization with mains missing, possible loose contact in electronics supply
04 Program watchdog has triggered
05 Actual value of armature current negative several times; armature current acquisition faulty
06 Firing pulse interval different from specified value
07 Mains voltage out of range (rated mains connection voltage 20%)
08 Reserved
09 "End of Conversion" ADC signal missing (analog data acquisition faulty)
10 Reserved
11 Reserved
12 Armature voltage value wrong at UA = 0 V (measured during booting)
13 Reserved
14 Phase failure, mains or power unit not connected (measured at Main contactor ON)
15 Not assigned
16 The drive blocks if 1) P086 is set to ON 2) the drive runs at the current limit for longer than the time set using P087 and, during this time, 3) the speed set with P078 is continually fallen short of
17 Armature circuit open, armature not connected, armature circuit fuse has tripped, wrong speed standardization with tachometer control (P083 = 0/1)
18 Data traffic interrupted for longer than 1200 ms (in the case of serial communication, no data was exchanged during the last 1.2 s). It is assumed that there is an interruption in the connection between the computer/controller and the power converter; with P001 = 1/2/3
19 Not assigned
20 Mains frequency out of upper or lower measuring range f < 44 Hz or f > 66 Hz
21 Reserved
22 Reserved
23 Reserved
24 Min. field current out of lower range (Field current < 50% of rated field current if no field weakening is set and field current < 50% of the minimum field current with field weakening
25 Not assigned
26 Not assigned
27 Program execution disturbed
28 Hardware defect in digital section
29 Armature current 0 message disturbed/ defective (is acquired during booting; without a message, the system does not switch in torque direction TD1)
30 Armature current measurement offset error (is determined during booting, armature current measurement is disturbed or defective)
31 Reserved
32 Reserved
33 Overcurrent bridge 1 (TD1) Armature current actual value > 2 * rated value
34 Overcurrent bridge 2 (TD2) Armature current actual value > 2 * rated value
35 Not assigned
36 Signal for mains synchronization missing (e.g. plug X10 loose)
37 Interface X11 defective Ribbon cable missing or defective
38 Tachometer/encoder wire break No speed actual value signal with P083 = 0/1/2/3 or wrong I*R value (P020) or armature circuit open
39 Actual value polarity wrong; tachometer/ encoder, field or armature connected wrongly with P083 = 0/1/2/3 or wrong I*R value
40 Tachometer offset error (is determined during booting, speed actual value measurement is disturbed or defective); e.g. RESET with rotating machine), with P083 = 0/1 only
41
S04.09 and above
Incremental encoder evaluation not available. Monitoring with controller structure P083 = 2/3 (at initialization of the power converter or data set loading only)
42 EEPROM data set X is not from the same software group
43 Not assigned
44 n>1.15*nrated, only with tachometer/encoder control P083 = 0/1/2/3 and errorfree tachometer generator/encoder
45 Field connection not correct Field connection not available or not connected in-phase
46 Power stage connection not correct (phase sequence incorrect)
47
S04.11 and above
Daughterboard (3.9217) for parallel nominal value setting is not available. The system checks at initialization of the power converter or data set loading (P008) only.
48 Not assigned
49 EEPROM formatting faulty
50 EEPROM not fitted or EEPROM storage area too small, error during EEPROM formatting
51 Checksum or boot data set termination faulty
52 EEPROM is not software-compatible EEPROM and program EEPROMs are not from the same software group
53 Boot data set is not from the same software group
54 EEPROM boot data set is too long
55 EEPROM can not be cleared (after carrying out P109)
56 Boot source entry in EEPROM is outside range or not available
57 EEPROM data set X is too long (with P008 or when using P099/4)
58 EEPROM data set X, checksum or data set termination not correct (with P008 or when using P099/4)
59 EEPROM data set X is not available (with P008 or when using P099/4)
60 Not assigned
61 No data set programmed
62 Device type is not software-compatible
63 Individual EEPROM datum defective, P001, P006, P007, P009 have values that are outside the limits
64 Not assigned
65 Reserved
66 Reserved
67 Reserved
68 Not assigned
69 Not assigned
70 Not assigned
71 Phase difference 90° synchronous filter
72 PC software and power converter software not compatible
73 PC data file and power converter software not compatible
74 Communication source outside range
75 Not assigned
76 Timeout exceeded programming individual datum
78
S04.23 and above
RAM defective
100 Power stage detection not possible
101 Power stage detection of field device not possible
102 Ripple limit cannot be determined (with optimization run 1 or 4.1) device current or current limit too low
103 Armature circuit inductivity cannot be determined with optimization run 1 or 4.1 Possibly P037 = 0.00
104 Motorized potentiometer memory value unusable (with P099/3)
105 Temperature of motor has exceeded the set threshold (I²t monitoring)
106 Mains frequency is outside the range of 47 Hz < f < 63 Hz, the power converter can still function
107 Temperature of heat sink in the power stage > 85° C
108 Temperature measurement of the heat sink in the power stage not possible
109 Verify error on data set programming with P004 = 1/2/3/4
110 Data set programming cancelled due to timeout being exceeded (max. of 5 s with P004 = 1/2/3/4)
111 Boot source entry is invalid
112 EEPROM data set was not programmed (data set not saved)
113 EEPROM data set was not loaded (P008 or P099/4)
114 Acceleration factor cannot be determined (P081 = 6/P136 = ON)
115 Entered maximum speed (P142) for selected rotary encoder (P143) is too high.